Whole-Wall R-Value & Thermal Bridge Calculator

Estimate effective whole-wall R-value and U-factor from insulated cavity and framing paths, then compare added continuous insulation.

Enter your values

Calculations run on your device; inputs are not sent to our server.

Core result

Use this for the whole opaque wall

Enter the thermal resistance of the insulated cavity path, the framing path and layers that cross both paths. The area-weighted result answers how repeating studs reduce the wall assembly value and whether more continuous insulation materially changes it.

Parallel-path formula and units

For framing fraction f, U = (1−f)/(R cavity + R common) + f/(R framing + R common), and effective R = 1/U. The same equation works in RSI. Conversion uses 1 US R = 0.176110184 m²·K/W. Continuous layers are added to both paths before area weighting.

Three independent checks

R-13 cavity, R-4.375 framing, R-2 common and 25% framing gives effective R-11.2088, U-factor 0.089216 and a 25.2747% reduction from the R-15 cavity path. Replacing R-2 common with R-7 gives R-16.8129 and cuts U by 33.3323%. R-21 cavity, R-6.875 framing, R-1 common and 23% framing gives R-15.5748. In SI, RSI 3 cavity, RSI 1 framing, RSI 0.5 common and 20% framing gives RSI 2.76316.

Interpretation, assumptions and limits

A lower U and higher effective R/RSI indicate less one-dimensional conductive heat flow. Use tested path values and a project-specific framing fraction. This estimate excludes windows, doors, corners not represented by f, air leakage, moisture, fasteners, thermal contact resistance, condensation, dynamic temperature effects and code compliance.

Sources and calculation scope

The parallel-path equation follows the U.S. DOE Building America advanced wall guidance; framing thermal bridging and continuous insulation context comes from DOE Building Science Education.

Unexpected result? Tell us the inputs and what you expected.