Plan an assembly, not a product claim
Enter the resistance already provided by the rest of the assembly, then add up to three insulation or finish layers using thickness and the product-rated resistance per unit thickness. The target is user supplied; the calculator does not choose a climate-zone or code requirement for you.
Formula, units and target thickness
Layer resistance = thickness × resistance per unit thickness. Total R or RSI = base resistance + the layer resistances. U-factor is the reciprocal: U = 1/R in US units and U = 1/RSI in SI units. The conversion used is 1 US R = 0.176110184 m²·K/W. If the target is higher, candidate thickness = (target − total) ÷ candidate resistance per unit thickness.
Three independent checks
Base R-0 plus 3.5 in at R-3.5/in gives R-12.25, RSI 2.15735 and U-factor 0.081633. Base R-2 plus 5.5 in at R-3.6/in gives R-21.8 and U-factor 0.045872. In SI, base RSI 0.35 plus 10 cm at 0.22 RSI/cm and 5 cm at 0.12 RSI/cm gives RSI 3.15, R-17.8865 and U-value 0.317460 W/(m²·K). A target RSI 4 using 0.22 RSI/cm needs 3.86364 cm more.
Read the result in the real assembly
Higher R/RSI means more resistance to heat flow; lower U means less heat transmission. Adding nominal layer R-values is a one-dimensional estimate. Framing, fasteners, gaps, compression, moisture, temperature, aging, air leakage and workmanship can reduce whole-assembly performance.
Sources and calculation scope
Use tested product values for the actual thickness and installation. This tool does not model parallel heat paths, thermal bridges, air films, condensation, HVAC load or code compliance. Official context: U.S. DOE Consumer Guide to Home Insulation and DOE Building America U-Factor guidance.