Use the whole-product label
Enter the NFRC whole-product U-factor when available, not center-of-glass data. U × area × temperature difference gives steady conductive heat flow. SHGC × unshaded irradiance × area estimates solar heat entering during the stated sunny hours.
Decision comparison
The alternative keeps the same window area, temperatures, irradiance and hours while changing U-factor and SHGC. Lower U reduces conduction in both seasons; lower SHGC reduces solar gain, which can help cooling but can also remove useful winter gain.
Three independent checks
Two 4 ft × 5 ft windows at U=0.30 and ΔT=40°F have 40 ft² area and 480 BTU/h conductive loss (140.674 W). Three 2 m × 1.5 m windows at U=1.4 W/(m²·K) and ΔT=20 K give 252 W. For 10 m², SHGC 0.40, 500 W/m² irradiance and 25% shading, solar gain is 1,500 W.
Inputs, interpretation and limits
Zero area, nonpositive U-factor, SHGC outside 0–1, shading outside 0–100%, and invalid temperatures are rejected. This is a steady-state screening estimate. It excludes air leakage, frame installation defects, thermal mass, changing weather, orientation profiles, HVAC efficiency, condensation and utility rates.
Sources and calculation scope
The NFRC label defines whole-product U-factor and SHGC. The U.S. Department of Energy explains window heat transfer and climate-oriented selection.