Wall Heat Loss, U-Value & R-Value Calculator

Estimate steady-state wall heat loss or gain from area, U-value or R-value, temperatures and time, then compare another assembly.

Enter your values

Calculations run on your device; inputs are not sent to our server.

Core result

Estimate one opaque wall

Enter the net wall area, tested whole-assembly U-value or R-value, indoor/outdoor design temperatures and duration. The result shows steady-state conductive heat loss or gain in W and Btu/h, plus kWh and kBtu over the entered time.

Heat-transfer formula and units

Q̇ = U × A × |Tin − Tout|. If R is entered, U = 1/R. In SI use W/(m²·K), m² and kelvins; in US customary use Btu/(h·ft²·°F), ft² and °F. Energy = rate × hours. Unit changes convert the entered area, temperatures and assembly value.

Three independent checks

For 200 ft², R-13, 70°F indoors and 30°F outdoors, rate = 615.3846 Btu/h = 180.351 W and 24-hour energy = 4.3284 kWh. R-20 under the same conditions gives 400 Btu/h, a 35% reduction. For 20 m², U=0.35, 21°C/1°C and 8 h, rate = 140 W and energy = 1.12 kWh. For 12 m², RSI 2.5, 20°C/−5°C and 24 h, rate = 120 W and energy = 2.88 kWh.

Decision use and limits

Use the optional scenario to compare two assembly U- or R-values under identical area, temperature and time. This is steady-state one-dimensional conduction only. It excludes windows and doors not removed from area, air leakage, solar gain, thermal mass, moisture, ground coupling, internal gains, HVAC efficiency and design safety factors. Do not size equipment from this result alone.

Sources and calculation scope

The formula follows DOE Building Science Education heat-loss guidance and the DOE Building America envelope reference.