Voltage Drop & Wire Comparison Calculator

Estimate resistive voltage drop, load voltage and conductor loss, then compare an alternate AWG and screen a user-entered drop limit.

Enter your values

Calculations run on your device; inputs are not sent to our server.

Core result

Enter the wire run and load

Use one-way length. Choose DC, single-phase AC or three-phase AC, then enter source voltage, current, conductor material, size and temperature. The core voltage loss appears before optional gauge decisions.

Formula and decision comparison

Conductor resistance is R=ρL/A. The resistive circuit drop is 2IR for DC or single phase and √3IR for three phase, where L is one-way length. Compare another AWG and screen the result against your own allowable percentage.

Independent checks

At 20°C, 30 m of 4 mm² copper carrying 20 A in a single-phase resistive circuit drops about 5.1724 V. At 400 V, 32 A, 50 m and 10 mm², the three-phase estimate is about 4.7779 V. Zero current produces zero drop. The default 12 AWG case includes a 75°C resistance adjustment.

Input mistakes, interpretation and limits

Do not double a round-trip length before entering it: the two-wire factor is already applied. Zero current is valid; required length, voltage and area must be positive. This is a resistive screening model, not a wire-safety selector. It excludes reactance, power factor, harmonics, connections, parallel conductors, ampacity, insulation, protection, local electrical code and installation conditions.

Official sources

The NIST copper wire tables give 20°C standard-annealed copper resistivity and the 0.00393/°C resistance coefficient. The aluminum value is a published reference estimate; verify the selected product data and governing code before installation.

Unexpected result? Tell us the inputs and what you expected.